Grigsby, L.L., Hanson, A.P., Schlueter, R.A., Alemadi, N." Power Systems The Electrical Engineering Handbook Ed. Richard C. Dorf Boca raton crc Press llc. 2000
Grigsby, L.L., Hanson, A.P., Schlueter, R.A., Alemadi, N. “Power Systems” The Electrical Engineering Handbook Ed. Richard C. Dorf Boca Raton: CRC Press LLC, 2000
63 Power systems 63.1 Power System Analysis Introduction. Types of Powe m Analyses. The Power Flow Problem. Formulation of the Bus Admittance Matrix. Example LL. Grigsby and Formulation of the Power Flow Equations. P-V Buses.Bus AP Hanson Classifications.Generalized Power Flow Development.Solution Auburn University Methods.componentPowerFlows R.A. Schlueter and 63.2 Voltage Instability Voltage Stability Overview. Voltage Stability Models and N. Alemadi Simulation Tools. Kinds, Classes, and Agents of voltage Michigan State University Instability. Proximity to Voltage Instability. Future Research 63.1 Power System analysis Introduction The equivalent circuit parameters of many power system components are described in Chapters 61, 64, and 66. The interconnection of the different elements allows development of an overall power system model. The stem model provides the basis for computational simulation of the system performance under a wide variety of projected operating conditions. Additionally, "post mortem"studies, performed after system disturbances or equipment failures, often provide valuable insight into contributing system conditions. The different types f power system analyses are discussed below; the type of analysis performed depends on the conditions to be Types of Power System Analyses Power Flow analysis Power systems typically operate under slowly changing conditions which can be analyzed using steady state analysis. Further, transmission systems operate under balanced or near balanced conditions allowing per phase point for many other analyses. For example, the small signal and transient stability effects of a given disturballs a analysis to be used with a high degree of confidence in the solution. Power flow analysis provides the starti are dramatically affected by the"pre-disturbance"operating conditions of the power system.(A disturbance resulting in instability under heavily loaded system conditions may not have any adverse effects under lightly loaded conditions. )Additionally, fault analysis and transient analysis can also be impacted by the "pre-distur bance"operating point of a power system(although, they are usually affected much less than transient stability and small signal stability analysis) Fault Analysis Fault analysis refers to power system analysis under severely unbalanced conditions. Such conditions inch downed or open conductors. Fault analysis assesses the system behavior under the high current and/or severely e 2000 by CRC Press LLC
© 2000 by CRC Press LLC 63 Power Systems 63.1 Power System Analysis Introduction • Types of Power System Analyses • The Power Flow Problem • Formulation of the Bus Admittance Matrix • Example Formulation of the Power Flow Equations • P-V Buses • Bus Classifications • Generalized Power Flow Development • Solution Methods • Component Power Flows 63.2 Voltage Instability Voltage Stability Overview • Voltage Stability Models and Simulation Tools • Kinds, Classes, and Agents of Voltage Instability • Proximity to Voltage Instability • Future Research 63.1 Power System Analysis Introduction The equivalent circuit parameters of many power system components are described in Chapters 61, 64, and 66. The interconnection of the different elements allows development of an overall power system model. The system model provides the basis for computational simulation of the system performance under a wide variety of projected operating conditions. Additionally, “post mortem” studies, performed after system disturbances or equipment failures, often provide valuable insight into contributing system conditions. The different types of power system analyses are discussed below; the type of analysis performed depends on the conditions to be assessed. Types of Power System Analyses Power Flow Analysis Power systems typically operate under slowly changing conditions which can be analyzed using steady state analysis. Further, transmission systems operate under balanced or near balanced conditions allowing per phase analysis to be used with a high degree of confidence in the solution. Power flow analysis provides the starting point for many other analyses. For example, the small signal and transient stability effects of a given disturbance are dramatically affected by the “pre-disturbance” operating conditions of the power system. (A disturbance resulting in instability under heavily loaded system conditions may not have any adverse effects under lightly loaded conditions.) Additionally, fault analysis and transient analysis can also be impacted by the “pre-disturbance” operating point of a power system (although, they are usually affected much less than transient stability and small signal stability analysis). Fault Analysis Fault analysis refers to power system analysis under severely unbalanced conditions. (Such conditions include downed or open conductors.) Fault analysis assesses the system behavior under the high current and/or severely L.L. Grigsby and A.P. Hanson Auburn University R.A. Schlueter and N. Alemadi Michigan State University
unbalanced conditions typical during faults. The results of fault analyses are used to size and apply syster protective devices(breakers, relays, etc. Fault analysis is discussed in more detail in Section 61.5. Transient Stability Analysis Transient stability analysis, unlike the analyses previously discussed, assesses the systems performance over a period of time. The system model for transient stability analysis typically includes not only the transmission network parameters, but also the dynamics data for the generators. Transient stability analysis is most often used to determine if individual generating units will maintain synchronism with the power system following a disturbance(typically a fault) Extended Stability analysis Extended stability analysis deals with system stability beyond the generating units' first swing. "In addition to the generator data required for transient stability analysis, extended stability analysis requires excitation system, d governor, and prime mover dynamic data. Often, extended stability analysis will also include dynamics data for control devices such as tap changing transformers, switched capacitors, and relays. The addition of these elements to the system model complicates the analysis, but provides comprehensive simulation of nearly all major system components and controls. Extended stability analyses complement small signal stability analyses by verifying the existence of persistent oscillations and establishing the magnitudes of power and/or Small Signal Stability Analysis Small signal stability assesses the stability of the power system when subjected to"small"perturbations. Small ignal stability uses a linearized model of the power system which includes generator, prime mover, and control device dynamics data. The system of nonlinear equations describing the system are linearized about a specific operating point and eigenvalues and eigenvectors of the linearized system found. The imaginary part of each eigenvalue indicates the frequency of the oscillations associated with the eigenvalue; the real part indicate damping of the oscillation. Usually, small signal stability analysis attempts to find disturbances and/or system conditions that can lead to sustained oscillations(indicated by small damping factors)in the power system. Small signal stability analysis does not provide oscillation magnitude information because the eigenvalues only indicate oscillation frequency and damping. Additionally, the controllability matrices(based on the linearized system)and the eigenvectors can be used to identify candidate generating units for application of new or improved controls(i.e, power system stabilizers and new or improved excitation systems) Transient analysis involves the analysis of the system (or at least several components of the system)when subjected to"fast"transients(i. e, lightning and switching transients). Transient analysis requires detailed component information which is often not readily available. Typically only system components in the immediate vicinity of the area of interest are modeled in transient analyses. Specialized software packages(most notably EMTP)are used to perform transient analyses perational analyses Several additional analyses used in the day-to-day operation of power systems are based on the results of the nalyses described above. Economic dispatch analyses determine the most economic real power output for each generating unit based on cost of generation for each unit and the system losses. Security or contingency analyses assess the systems ability to withstand the sudden loss of one or more major elements without overloading the remaining system. State estimation determines the"best"estimate of the real-time system state based on a redundant set of syster Im measuremen The power flow problem Power flow analysis is fundamental to the study of power systems. In fact, power flow forms the core of power system analysis. a power flow study is valuable for many reasons. For example, power flow analyses play a key role in the planning of additions or expansions to transmission and generation facilities. a power flow solution e 2000 by CRC Press LLC
© 2000 by CRC Press LLC unbalanced conditions typical during faults. The results of fault analyses are used to size and apply system protective devices (breakers, relays, etc.) Fault analysis is discussed in more detail in Section 61.5. Transient Stability Analysis Transient stability analysis, unlike the analyses previously discussed, assesses the system’s performance over a period of time. The system model for transient stability analysis typically includes not only the transmission network parameters, but also the dynamics data for the generators. Transient stability analysis is most often used to determine if individual generating units will maintain synchronism with the power system following a disturbance (typically a fault). Extended Stability Analysis Extended stability analysis deals with system stability beyond the generating units’ “first swing.” In addition to the generator data required for transient stability analysis, extended stability analysis requires excitation system, speed governor, and prime mover dynamic data. Often, extended stability analysis will also include dynamics data for control devices such as tap changing transformers, switched capacitors, and relays. The addition of these elements to the system model complicates the analysis, but provides comprehensive simulation of nearly all major system components and controls. Extended stability analyses complement small signal stability analyses by verifying the existence of persistent oscillations and establishing the magnitudes of power and/or voltage oscillations. Small Signal Stability Analysis Small signal stability assesses the stability of the power system when subjected to “small” perturbations. Small signal stability uses a linearized model of the power system which includes generator, prime mover, and control device dynamics data. The system of nonlinear equations describing the system are linearized about a specific operating point and eigenvalues and eigenvectors of the linearized system found. The imaginary part of each eigenvalue indicates the frequency of the oscillations associated with the eigenvalue; the real part indicates damping of the oscillation. Usually, small signal stability analysis attempts to find disturbances and/or system conditions that can lead to sustained oscillations (indicated by small damping factors) in the power system. Small signal stability analysis does not provide oscillation magnitude information because the eigenvalues only indicate oscillation frequency and damping. Additionally, the controllability matrices (based on the linearized system) and the eigenvectors can be used to identify candidate generating units for application of new or improved controls (i.e., power system stabilizers and new or improved excitation systems). Transient Analysis Transient analysis involves the analysis of the system (or at least several components of the system) when subjected to “fast” transients (i.e., lightning and switching transients). Transient analysis requires detailed component information which is often not readily available. Typically only system components in the immediate vicinity of the area of interest are modeled in transient analyses. Specialized software packages (most notably EMTP) are used to perform transient analyses. Operational Analyses Several additional analyses used in the day-to-day operation of power systems are based on the results of the analyses described above. Economic dispatch analyses determine the most economic real power output for each generating unit based on cost of generation for each unit and the system losses. Security or contingency analyses assess the system’s ability to withstand the sudden loss of one or more major elements without overloading the remaining system. State estimation determines the “best” estimate of the real-time system state based on a redundant set of system measurements. The Power Flow Problem Power flow analysis is fundamental to the study of power systems. In fact, power flow forms the core of power system analysis. A power flow study is valuable for many reasons. For example, power flow analyses play a key role in the planning of additions or expansions to transmission and generation facilities. A power flow solution
ogEn FIGURE 63.1 The one line diagram of a power system is often the starting point for many other types of power system analyses. In addition, power flow analysis and many of its extensions are an essential ingredient of the studies performed in power system operations. In this latter case, it is at the heart of contingency analysis and the implementation of real-time monitoring systems The power flow problem(popularly known as the load flow problem) can be stated as follows For a given power network, with known complex power loads and some set of specifications or restrictions on power generations and voltages, solve for any unknown bus voltages and unspecified generation and finally for the complex power flow in the network Additionally, the losses in individual components and the total network as a whole are usually calculated. Furthermore, the system is often checked for component overloads and voltages outside allowable tolerances Balanced operation is assumed for most power flow studies and will be assumed in this chapter. Consequently the positive sequence network is used for the analysis. In the solution of the power flow problem, the network element values are almost always taken to be in per unit. Likewise, the calculations within the power flow analysis are typically in per unit. However, the solution is usually expressed in a mixed format. Solution voltages are usually expressed in per unit; powers are most often given in kVA or MVA The " given network " may be in the form of a system map and accompanying data tables for the network components. More often, however, the network structure is given in the form of a one-line diagran Regardless of the form of the given network and how the network data are given, the steps to be followed in a power flow study can be summarized as follows 1. Determine element values for passive network components 2. Determine locations and values of all complex power loads. 3. Determine generation specifications and constraints. 4. Develop a mathematical model describing power flow in the network. 5. Solve for the voltage profile of the network. e 2000 by CRC Press LLC
© 2000 by CRC Press LLC is often the starting point for many other types of power system analyses. In addition, power flow analysis and many of its extensions are an essential ingredient of the studies performed in power system operations. In this latter case, it is at the heart of contingency analysis and the implementation of real-time monitoring systems. The power flow problem (popularly known as the load flow problem) can be stated as follows: For a given power network, with known complex power loads and some set of specifications or restrictions on power generations and voltages, solve for any unknown bus voltages and unspecified generation and finally for the complex power flow in the network components. Additionally, the losses in individual components and the total network as a whole are usually calculated. Furthermore, the system is often checked for component overloads and voltages outside allowable tolerances. Balanced operation is assumed for most power flow studies and will be assumed in this chapter. Consequently, the positive sequence network is used for the analysis. In the solution of the power flow problem, the network element values are almost always taken to be in per unit. Likewise, the calculations within the power flow analysis are typically in per unit. However, the solution is usually expressed in a mixed format. Solution voltages are usually expressed in per unit; powers are most often given in kVA or MVA. The “given network” may be in the form of a system map and accompanying data tables for the network components. More often, however, the network structure is given in the form of a one-line diagram (such as shown in Fig. 63.1). Regardless of the form of the given network and how the network data are given, the steps to be followed in a power flow study can be summarized as follows: 1. Determine element values for passive network components. 2. Determine locations and values of all complex power loads. 3. Determine generation specifications and constraints. 4. Develop a mathematical model describing power flow in the network. 5. Solve for the voltage profile of the network. FIGURE 63.1 The one line diagram of a power system
FIGURE 63.2 Off nominal turns ratio transformer flows and losses in the network. 7. Check for constraint violations Formulation of the bus admittance matrix The first step in developing the mathematical model describing the power flow in the network is the formulation of the bus admittance matrix. the bus admittance matrix is an nxn matrix(where n is the number of buses in the system) constructed from the admittances of the equivalent circuit elements of the segments making up the power system. Most system segments are represented by a combination of shunt elements(connected between a bus and the reference node) and series elements(connected between two system buses). Formulation of the bus admittance matrix follows two simple rules: 1. The admittance of elements connected between node k and reference is added to the(k, k)entry of the 2. The admittance of elements connected between nodes j and k is added to the(])and(k, k)entries of the admittance matrix. The negative of the admittance is added to the (i, k)and (k, j) entries of the admittance matrix Off nominal transformers(transformers with transformation ratios different from the system voltage bases at the terminals) present some special difficulties. Figure 63. 2 shows a representation of an off nominal turns ratio transformer The admittance matrix mathematical model of an isolated off nominal transformer is Y -C"Y. Yelv where e is the equivalent series admittance (referred to node j c is the complex(off nominal)turns ratio , is the current injected at node j is the voltage at node j(with respect to reference) Off nominal transformers are added to the bus admittance matrix by adding the corresponding entry of the isolated off nominal transformer admittance matrix to the system bus admittance matrix. Example Formulation of the Power Flow Equations Considerable insight into the power flow problem and its properties and characteristics can be obtained by consideration of a simple example before proceeding to a general formulation of the problem. This simple case will also serve to establish some notation e 2000 by CRC Press LLC
© 2000 by CRC Press LLC 6. Solve for the power flows and losses in the network. 7. Check for constraint violations. Formulation of the Bus Admittance Matrix The first step in developing the mathematical model describing the power flow in the network is the formulation of the bus admittance matrix. The bus admittance matrix is an n×n matrix (where n is the number of buses in the system) constructed from the admittances of the equivalent circuit elements of the segments making up the power system. Most system segments are represented by a combination of shunt elements (connected between a bus and the reference node) and series elements (connected between two system buses). Formulation of the bus admittance matrix follows two simple rules: 1. The admittance of elements connected between node k and reference is added to the (k, k) entry of the admittance matrix. 2. The admittance of elements connected between nodes j and k is added to the (j, j) and (k, k) entries of the admittance matrix. The negative of the admittance is added to the (j, k) and (k, j) entries of the admittance matrix. Off nominal transformers (transformers with transformation ratios different from the system voltage bases at the terminals) present some special difficulties. Figure 63.2 shows a representation of an off nominal turns ratio transformer. The admittance matrix mathematical model of an isolated off nominal transformer is: (63.1) where – Ye is the equivalent series admittance (referred to node j) – c is the complex (off nominal) turns ratio – Ij is the current injected at node j – Vj is the voltage at node j (with respect to reference) Off nominal transformers are added to the bus admittance matrix by adding the corresponding entry of the isolated off nominal transformer admittance matrix to the system bus admittance matrix. Example Formulation of the Power Flow Equations Considerable insight into the power flow problem and its properties and characteristics can be obtained by consideration of a simple example before proceeding to a general formulation of the problem. This simple case will also serve to establish some notation. FIGURE 63.2 Off nominal turns ratio transformer. I I Y cY -c*Y c Y V V j k e e e e j k = − 2
Net work One-line Di FIGURE 63.3 Conceptual one-line diagram of a four-bus power system A conceptual representation of a one-line diagram for a four-bus power system is shown in Fig. 63.3. For generality, a generator and a load are shown connected to each bus. The following notation applies 1= Complex complex power flow into bus I from the generator Complex complex power flow into the load from bus Comparable quantities for the complex power generations and loads are obvious for each of the three other The positive sequence network for the power system represented by the one-line diagram of Fig 63.3 is shown in Fig. 63. 4. The boxes symbolize the combination of generation and load Network texts refer to this network as a five-node network. (The balanced nature of the system allows analysis using only the positive quence network; reducing each three-phase bus to a single node. The reference or ground represents the fifth node. )However, in power systems literature it is usually referred to as a four-bus network or power system. For the network of Fig 63.4, we define the following additional notation: S,=SGi- Spi Net complex power injected at bus 1 I1 Net positive sequence phasor current injected at bus 1 VI= Positive sequence phasor voltage at bus The standard node voltage equations for the network can be written in terms of the quantities at bus 1 (defined above)and comparable quantities at the other buses. e 2000 by CRC Press LLC
© 2000 by CRC Press LLC A conceptual representation of a one-line diagram for a four-bus power system is shown in Fig. 63.3. For generality, a generator and a load are shown connected to each bus. The following notation applies: – SG1 = Complex complex power flow into bus 1 from the generator – SD1 = Complex complex power flow into the load from bus 1 Comparable quantities for the complex power generations and loads are obvious for each of the three other buses. The positive sequence network for the power system represented by the one-line diagram of Fig. 63.3 is shown in Fig. 63.4. The boxes symbolize the combination of generation and load. Network texts refer to this network as a five-node network. (The balanced nature of the system allows analysis using only the positive sequence network; reducing each three-phase bus to a single node. The reference or ground represents the fifth node.) However, in power systems literature it is usually referred to as a four-bus network or power system. For the network of Fig. 63.4, we define the following additional notation: – S1 = – SG1 – – SD1 Net complex power injected at bus 1 – I1 = Net positive sequence phasor current injected at bus 1 – V1 = Positive sequence phasor voltage at bus 1 The standard node voltage equations for the network can be written in terms of the quantities at bus 1 (defined above) and comparable quantities at the other buses. FIGURE 63.3 Conceptual one-line diagram of a four-bus power system
Net work PassIve Component Neutral FIGURE 63.4 Positive sequence network for the system of Fig 63.3 II=YV+Yv2+Yv3+ Yv (63.2) 2=Y21V1+Y2y2+Y23V3+Y24V4 (63.3) YV+Yv+Y. L4=Y4V+Y2v2+Yv,+Y4V4 (63.5) The admittances in Eqs. (63. 2)through(63.5), Yi> are the ijth entries of the bus admittance matrix for the ower system. The unknown voltages could be found using linear algebra if the four currents I.I were known. However, these currents are not known. Rather, something is known about the complex power and voltage at each bus. The complex power injected into bus k of the power system is defined by the relationship between complex power, voltage, and current given by Eq (63.6 S, =VI Therefore (63.7) By substituting this result into the nodal equations and rearranging, the basic power flow equations for the four-bus system are given as Eqs. (63. 8)through(63. 11) SGI-SDI=VY,V,+Y12 V2+Y,,+Y, (63.8) e 2000 by CRC Press LLC
© 2000 by CRC Press LLC (63.2) (63.3) (63.4) (63.5) The admittances in Eqs. (63.2) through (63.5), – Yij, are the ijth entries of the bus admittance matrix for the power system. The unknown voltages could be found using linear algebra if the four currents – I1… – I4 were known. However, these currents are not known. Rather, something is known about the complex power and voltage at each bus. The complex power injected into bus k of the power system is defined by the relationship between complex power, voltage, and current given by Eq. (63.6). (63.6) Therefore, (63.7) By substituting this result into the nodal equations and rearranging, the basic power flow equations for the four-bus system are given as Eqs. (63.8) through (63.11) (63.8) FIGURE 63.4 Positive sequence network for the system of Fig. 63.3. I YV YV YV YV 1 11 1 12 2 13 3 14 4 =+++ I YV YV YV YV 2 21 1 22 2 23 3 24 4 =+++ I YV YV YV YV 3 31 1 32 2 33 3 34 4 =+++ I YV YV YV YV 4 41 1 42 2 43 3 44 4 =+++ S VI k kk * = I S V S S V k k * k * Gk * Dk * k * = = − SG1 – S V YV YV YV YV * D1 * 1 * 11 1 12 2 13 3 14 4 = +++ [ ]
-5=V2Y2V1+Y2V2+Y2V3+Y2V Sp3=V Y,,+Y32V2 SG4-Sp4=VYV,+YV2+Y,V,+Y,v. (63.11) Examination of Eqs.(63.8)through(63 11)reveals that, except for the trivial case where the generation equals the load at every bus, the complex power outputs of the generators cannot be arbitrarily selected. In fact, the complex power output of at least one of the generators must be calculated last because it must take up the unknown"slack"due to the, as yet, uncalculated network losses. Further, losses cannot be calculated until the voltages are known. These observations are a result of the principle of conservation of complex power (i.e, the sum of the injected complex powers at the four system buses is equal to the system complex power losses Further examination of Eqs. (63.8)through(63. 11)indicates that it is not possible to solve these equations or the absolute phase angles of the phasor voltages. This simply means that the problem can only be solved to some arbitrary phase angle reference. In order to alleviate the dilemma outlined above, suppose Sga is arbitrarily allowed to float or swing(in order to take up the necessary slack caused by the losses)and that SGl Sgz, and Sa are specified (other cases will be considered shortly). Now, with the loads known, Eqs.(63.7)through(63. 10)are seen as four simulta neous nonlinear equations with complex coefficients in five unknowns Vi, V2, V3, va, and The problem of too many unknowns(which would result in an infinite number of solutions) is solved by ecifying another variable Designating bus 4 as the slack bus and specifying the voltage V, reduces the proble to four equations in four unknowns. The slack bus is chosen as the phase reference for all phasor calculations, its magnitude is constrained, and the complex power generation at this bus is free to take up the slack necessary in order to account for the system real and reactive power losses. The specification of the voltage V, decouples Eq (63. 11)from Eqs.(63.8)through(63. 10), allowing calcu lation of the slack bus complex power after solving the remaining equations. (This property carries over larger systems with any number of buses. )The example problem is reduced to solving only three equations lultaneously for the unknowns VI, V2, and V3. Similarly, for the case of n buses, it is necessary to solve n-1 simultaneous, complex coefficient, nonlinear equations. Systems of nonlinear equations, such as Eqs. (63. 8)through(63. 10), cannot(except in rare cases)be solved by closed-form techniques. Direct simulation was used extensively for many years; however, essentially all power flow analyses today are performed using iterative techniques on digital computers P-V Buses In all realistic cases, the voltage magnitude is specified at generator buses to take advantage of the generator's reactive power capability. Specifying the voltage magnitude at a generator bus requires a variable specified in the simple analysis discussed earlier to become an unknown (in order to bring the number of unknowns back into correspondence with the number of equations). Normally, the reactive power injected by the generator becomes a variable, leaving the real power and voltage magnitude as the specified quantities at the generator bus It was noted earlier that Eq (63. 11) is decoupled and only Eqs. (63.8)through(63.10)need be solved simultaneously. Although not immediately apparent, specifying the voltage magnitude at a bus and treating the bus reactive power injection as a variable results in retention of, effectively, the same number of complex unknowns. For example, if the voltage magnitude of bus I of the earlier four bus system is specified and the reactive power injection at bus 1 becomes a variable, Eqs.(63. 8)through(63. 10)again effectively have three complex unknowns. (The phasor voltages V2 and V3 at buses 2 and 3 are two complex unknowns and the angle 8, of the voltage at bus 1 plus the reactive power generation QGi at bus 1 result in the equivalent of a hird complex unknown) e 2000 by CRC Press LLC
© 2000 by CRC Press LLC (63.9) (63.10) (63.11) Examination of Eqs. (63.8) through (63.11) reveals that, except for the trivial case where the generation equals the load at every bus, the complex power outputs of the generators cannot be arbitrarily selected. In fact, the complex power output of at least one of the generators must be calculated last because it must take up the unknown “slack” due to the, as yet, uncalculated network losses. Further, losses cannot be calculated until the voltages are known. These observations are a result of the principle of conservation of complex power (i.e., the sum of the injected complex powers at the four system buses is equal to the system complex power losses). Further examination of Eqs. (63.8) through (63.11) indicates that it is not possible to solve these equations for the absolute phase angles of the phasor voltages. This simply means that the problem can only be solved to some arbitrary phase angle reference. In order to alleviate the dilemma outlined above, suppose – SG4 is arbitrarily allowed to float or swing (in order to take up the necessary slack caused by the losses) and that – SG1, – SG2, and – SG3 are specified (other cases will be considered shortly). Now, with the loads known, Eqs. (63.7) through (63.10) are seen as four simultaneous nonlinear equations with complex coefficients in five unknowns – V1, – V2, – V3, – V4, and – SG4 . The problem of too many unknowns (which would result in an infinite number of solutions) is solved by specifying another variable. Designating bus 4 as the slack bus and specifying the voltage – V4 reduces the problem to four equations in four unknowns. The slack bus is chosen as the phase reference for all phasor calculations, its magnitude is constrained, and the complex power generation at this bus is free to take up the slack necessary in order to account for the system real and reactive power losses. The specification of the voltage – V4 decouples Eq. (63.11) from Eqs. (63.8) through (63.10), allowing calculation of the slack bus complex power after solving the remaining equations. (This property carries over to larger systems with any number of buses.) The example problem is reduced to solving only three equations simultaneously for the unknowns – V1, – V2 , and – V3 . Similarly, for the case of n buses, it is necessary to solve n-1 simultaneous, complex coefficient, nonlinear equations. Systems of nonlinear equations, such as Eqs. (63.8) through (63.10), cannot (except in rare cases) be solved by closed-form techniques. Direct simulation was used extensively for many years; however, essentially all power flow analyses today are performed using iterative techniques on digital computers. P-V Buses In all realistic cases, the voltage magnitude is specified at generator buses to take advantage of the generator’s reactive power capability. Specifying the voltage magnitude at a generator bus requires a variable specified in the simple analysis discussed earlier to become an unknown (in order to bring the number of unknowns back into correspondence with the number of equations). Normally, the reactive power injected by the generator becomes a variable, leaving the real power and voltage magnitude as the specified quantities at the generator bus. It was noted earlier that Eq. (63.11) is decoupled and only Eqs. (63.8) through (63.10) need be solved simultaneously. Although not immediately apparent, specifying the voltage magnitude at a bus and treating the bus reactive power injection as a variable results in retention of, effectively, the same number of complex unknowns. For example, if the voltage magnitude of bus 1 of the earlier four bus system is specified and the reactive power injection at bus 1 becomes a variable, Eqs. (63.8) through (63.10) again effectively have three complex unknowns. (The phasor voltages – V2 and – V3 at buses 2 and 3 are two complex unknowns and the angle δ1 of the voltage at bus 1 plus the reactive power generation QG1 at bus 1 result in the equivalent of a third complex unknown.) SG2 – S V YV YV YV YV * D2 * 2 * 21 1 22 2 23 3 24 4 = +++ [ ] SG3 – S V YV YV YV YV * D3 * 3 * 31 1 32 2 33 3 34 4 = +++ [ ] SG4 – S V YV YV YV YV * D4 * 4 * 41 1 42 2 43 3 44 4 = +++ [ ]
Bus 1 is called a voltage controlled bus because it is apparent that the reactive power generation at bus 1 is being used to control the voltage magnitude. This type of bus is also referred to as a p-v bus because of the specified quantities. Typically, all generator buses are treated as voltage controlled buses Bus Classifications There are four quantities of interest associated with each bus: al power, 2. reactive power, Q 3. itude. v At every bus of the system two of these four quantities will be specified and the remaining two will be unknowns. Each of the system buses may be classified in accordance with the two quantities specified. The following classifications are typical Slack bus--The slack bus for the system is a single bus for which the voltage magnitude and angle are specified. The real and reactive power are unknowns. The bus selected as the slack bus must have a source of both real and reactive power, because the injected power at this bus must"swing"to take up the "slack "in the solution the best choice for the slack bus(since, in most power systems, many buses have eal and reactive power sources)requires experience with the particular system under study. The behavior of the solution is often influenced by the bus chosen. ( In the earlier discussion, the last bus was selected as the slack bus for convenience. Load bus(P-Q bus)-A load bus is defined as any bus of the system for which the real and reactive power specified Load buses may contain generators with specified real and reactive power outputs; however, wer as a Voltage controlled bus(P-V bus)Any bus for which the voltage magnitude and the injected real power are specified is classified as a voltage controlled (or P-v) bus. The injected reactive power is a variable(with pecified upper and lower bounds) in the power flow analysis. (A P-v bus must have a variable source of reactive power such as a generator or a capacitor bank Generalized Power Flow Development The more general(n bus)case is developed by extending the results of the simple four-bus example. Consider the case of an n-bus system and the corresponding n+l node positive sequence network. Assume that the buses are numbered such that the slack bus is numbered last. Direct extension of the earlier equations(writing the node voltage equations and making the same substitutions as in the four-bus case) yields the basic power flow The Basic Power Flow Equations(PFE s=B-jQk=VΣYV fork=1,2,3,,n-1 P-jQ=V2Y V (63.13) e 2000 by CRC Press LLC
© 2000 by CRC Press LLC Bus 1 is called a voltage controlled bus because it is apparent that the reactive power generation at bus 1 is being used to control the voltage magnitude. This type of bus is also referred to as a P-V bus because of the specified quantities. Typically, all generator buses are treated as voltage controlled buses. Bus Classifications There are four quantities of interest associated with each bus: 1. real power, P 2. reactive power, Q 3. voltage magnitude, V 4. voltage angle, δ At every bus of the system two of these four quantities will be specified and the remaining two will be unknowns. Each of the system buses may be classified in accordance with the two quantities specified. The following classifications are typical: • Slack bus—The slack bus for the system is a single bus for which the voltage magnitude and angle are specified. The real and reactive power are unknowns. The bus selected as the slack bus must have a source of both real and reactive power, because the injected power at this bus must “swing” to take up the “slack” in the solution. The best choice for the slack bus (since, in most power systems, many buses have real and reactive power sources) requires experience with the particular system under study. The behavior of the solution is often influenced by the bus chosen. (In the earlier discussion, the last bus was selected as the slack bus for convenience.) • Load bus (P-Q bus)—A load bus is defined as any bus of the system for which the real and reactive power are specified. Load buses may contain generators with specified real and reactive power outputs; however, it is often convenient to designate any bus with specified injected complex power as a load bus. • Voltage controlled bus (P-V bus)—Any bus for which the voltage magnitude and the injected real power are specified is classified as a voltage controlled (or P-V) bus. The injected reactive power is a variable (with specified upper and lower bounds) in the power flow analysis. (A P-V bus must have a variable source of reactive power such as a generator or a capacitor bank.) Generalized Power Flow Development The more general (n bus) case is developed by extending the results of the simple four-bus example. Consider the case of an n-bus system and the corresponding n+1 node positive sequence network. Assume that the buses are numbered such that the slack bus is numbered last. Direct extension of the earlier equations (writing the node voltage equations and making the same substitutions as in the four-bus case) yields the basic power flow equations in the general form. The Basic Power Flow Equations (PFE) (63.12) and (63.13) S P jQ V Y V for k = 1, 2, 3, , n – 1 k * k kk * ki i n i =1 =− = ∑ … P jQ V Y V n nn * ni i n i =1 − = ∑
quation(63.13)is the equation for the slack bus Equation(63. 12)represents n-1 simultaneous equations in n-1 complex unknowns if all buses(other than the slack bus)are classified as load buses. Thus, given a set of specified loads, the problem is to solve Eq (63.12)for the n-1 complex phasor voltages at the remaining buses ges are Eq (63.13)can be used to calcul Bus j is normally treated as a p-V bus if it has a directly connected generator. The unknowns at bus jare then the reactive generation QG and because the voltage magnitude, Vi, and the real power generation, P The next step in the analysis is to solve Eq (63. 12)for the bus voltages using some iterative method. Once he bus voltages have been found, the complex power flows and complex power losses in all of the network components are calculated. Solution methods The solution of the simultaneous nonlinear power flow equations requires the use of iterative techniques for even the simplest power systems. Although there are many methods for solving nonlinear equations, only two The Newton-Raphson Method The Newton-Raphson algorithm has been applied in the solution of nonlinear equations in many fields. The algorithm will be developed using a general set of two equations(for simplicity ). The results are easily extended to an arbitrary number of equations A set of two nonlinear equations are shown in Eqs. (63. 14)and(63. 15) f1(x1,x2 (63.14) f2(x1,x2)=k2 (63.15) Now, if x,(o) and x, fo) are inexact solution estimates and Ax(o) and Ax(o) are the corrections to the estimates an exact solution, Eqs. (63.14)and(63. 15 )can be rewritten as f1(x1+△x10,x2+△x20)=k1 (63.16) f2(x1+△x1 +△x,(0) (63.17) Expanding Eqs.(6316)and (63. 17)in a Taylor series about the estimate yields af af f(x9,x)+ △x+ of2 Axu+hot (63.19) where the superscript, (0), on the partial derivatives indicates evaluation of the partial derivatives at the initial estimate and h.o. t. indicates the higher order terms. 9, Neglecting the higher order terms(an acceptable approximation if Ax(o) and Axfo) are small), Eqs.(63.18) nd(63. 19) can be rearranged and written in matrix form. e 2000 by CRC Press LLC
© 2000 by CRC Press LLC Equation (63.13) is the equation for the slack bus. Equation (63.12) represents n-1 simultaneous equations in n-1 complex unknowns if all buses (other than the slack bus) are classified as load buses. Thus, given a set of specified loads, the problem is to solve Eq. (63.12) for the n-1 complex phasor voltages at the remaining buses. Once the bus voltages are known, Eq. (63.13) can be used to calculate the slack bus power. Bus j is normally treated as a P-V bus if it has a directly connected generator. The unknowns at bus j are then the reactive generation QGj and δj because the voltage magnitude, Vj , and the real power generation, Pgj , have been specified. The next step in the analysis is to solve Eq. (63.12) for the bus voltages using some iterative method. Once the bus voltages have been found, the complex power flows and complex power losses in all of the network components are calculated. Solution Methods The solution of the simultaneous nonlinear power flow equations requires the use of iterative techniques for even the simplest power systems. Although there are many methods for solving nonlinear equations, only two methods are discussed here. The Newton-Raphson Method The Newton-Raphson algorithm has been applied in the solution of nonlinear equations in many fields. The algorithm will be developed using a general set of two equations (for simplicity). The results are easily extended to an arbitrary number of equations. A set of two nonlinear equations are shown in Eqs. (63.14) and (63.15). f1(x1, x2) = k1 (63.14) f2(x1, x2) = k2 (63.15) Now, if x1 (0) and x2 (0) are inexact solution estimates and ∆x1 (0) and ∆x2 (0) are the corrections to the estimates to achieve an exact solution, Eqs. (63.14) and (63.15) can be rewritten as: f1(x1+ ∆x1 (0), x2+ ∆x2 (0)) = k1 (63.16) f2(x1+ ∆x1 (0), x2+ ∆x2 (0)) = k2 (63.17) Expanding Eqs. (63.16) and (63.17) in a Taylor series about the estimate yields: (63.18) (63.19) where the superscript, (0), on the partial derivatives indicates evaluation of the partial derivatives at the initial estimate and h.o.t. indicates the higher order terms. Neglecting the higher order terms (an acceptable approximation if ∆x1 (0) and ∆x2 (0) are small), Eqs. (63.18) and (63.19) can be rearranged and written in matrix form. f x ,x f x x f x x h.o.t. k 1 1 (0) 2 (0) 1 1 (0) 1 (0) 1 2 (0) 2 (0) ( ) 1 + + += ∂ ∂ ∂ ∂ ∆ ∆ f x ,x f x x f x x h.o.t. k 1 1 (0) 2 (0) 2 1 (0) 1 (0) 2 2 (0) 2 (0) ( ) 2 + + += ∂ ∂ ∂ ∂ ∆ ∆